Wiring & Cable

How to Calculate Voltage Drop

Learning how to calculate voltage drop matters because every metre of cable is a resistor in series with your load — and on a long run it can swallow more voltage than you expect.

Cable run showing progressive voltage loss along its length
Contents

Key takeaways

  • Drop is V = I × R₊ₐ₋ₓₑ — ordinary Ohm's law.
  • Count both conductors: current flows out and back.
  • Aim for under 3% on a final circuit, 5% overall.
  • The lost voltage becomes heat inside the cable.

Why cable resistance matters

Copper is a good conductor, not a perfect one. A 2.5 mm² conductor has roughly 7.4 mΩ per metre. Over a 40 m run there and back — 80 m of conductor — that is 0.59 Ω. At 16 A the drop is 9.5 V, and 152 W is being turned into heat inside the wall.

The formulas

DC and single-phase AC

  • Vₔₓₒₕ = (2 × ρ × L × I) ÷ A

The factor of 2 accounts for the return conductor. ρ is resistivity in Ω·m, L the one-way length in metres, I the current in amperes and A the cross-section in m².

Three-phase AC

  • Vₔₓₒₕ = (√3 × ρ × L × I) ÷ A

Balanced three-phase has no neutral return current, so the multiplier becomes √3 ≈ 1.732 instead of 2 — about 13% less drop for the same load.

Resistivity values at 20 °C

Conductor resistivity
Materialρ (Ω·m)Relative to copper
Silver1.59 × 10⁻⁸0.92
Copper (annealed)1.72 × 10⁻⁸1.00
Aluminium2.82 × 10⁻⁸1.64
Iron9.71 × 10⁻⁸5.65

Voltage Drop CalculatorEnter length, current, conductor size and circuit type for the drop in volts, percent and watts lost.

Open calculator

A worked example

A 230 V single-phase circuit feeds a 16 A load 35 m away through 4 mm² copper.

  1. Conductor length: 2 × 35 = 70 m
  2. Area in m²: 4 mm² = 4 × 10⁻⁶ m²
  3. Resistance: (1.72 × 10⁻⁸ × 70) ÷ (4 × 10⁻⁶) = 0.301 Ω
  4. Drop: 16 × 0.301 = 4.82 V
  5. Percentage: 4.82 ÷ 230 = 2.1% ✓
  6. Power lost: 16² × 0.301 = 77 W

Inside the 3% guideline, though 77 W of continuous heat is a real cost over a year — the electricity calculator puts a figure on it.

Acceptable limits

Common design targets (always confirm against local wiring rules)
CircuitTypical limitWhy
Lighting final circuit3%Visible dimming and colour shift
Power final circuit5%Motor starting torque
Supply to final board2%Leaves headroom downstream
Low-voltage DC (12 V)3%Only 0.36 V of margin available

Low-voltage systems are far less forgiving. A 1 V drop is 0.4% of 230 V but 8% of 12 V, which is why solar, automotive and LED-strip wiring so often needs conductors that look oversized.

Reducing the drop

  • Increase the cross-section. Drop is inversely proportional to area — doubling it halves the drop. See wire gauge and amp rating.
  • Shorten the run. Move the distribution point closer to the load.
  • Raise the supply voltage. The same power at twice the voltage halves the current and quarters the loss.
  • Split the load. Two circuits each carry half the current.
  • Choose copper over aluminium where space is tight — aluminium needs about 64% more area for the same drop.

Temperature matters too

Copper resistance rises about 0.393% per °C. A conductor at 70 °C has roughly 20% more resistance than the 20 °C figure, so a run that calculates at 2.5% cold can reach 3% when fully loaded. Our guide to the resistivity of copper covers the correction.

Measuring drop on an installed circuit

Calculation predicts the drop; measurement confirms it, and finds the faults a calculation cannot.

  1. Load the circuit to its normal running current — drop only appears when current flows.
  2. Measure the voltage at the origin, then at the load, without changing the loading.
  3. The difference is the actual drop across both conductors.

If the measured drop is much larger than calculated, the cable is rarely the problem. Look for a loose terminal, a corroded joint or an undersized connector — a single bad termination can add more resistance than tens of metres of conductor.

Drop across a connection

Measuring directly across a suspect joint while it is loaded is the quickest diagnostic there is. A sound termination shows a few millivolts. Anything approaching a volt is dissipating real power in a small space, and that is how connections overheat.

Check it before you pull cable

The voltage drop calculator at Ohms Law Wheel handles DC, single-phase and three-phase, accepts mm² or AWG, and reports the drop in volts, as a percentage and in watts lost — so you can compare two conductor sizes before committing to either.

Frequently asked questions

What is an acceptable voltage drop?

Around 3% for a lighting final circuit and 5% for power circuits is the common design target, with roughly 2% allowed between the origin and a distribution board. Always confirm against the wiring regulations that apply where you are.

Why do I multiply the cable length by two?

Because current flows out along one conductor and back along the other. A 35 m run means 70 m of conductor in the circuit, so the resistance doubles.

Does voltage drop waste energy?

Yes. The dropped voltage times the current is power dissipated as heat in the cable. A 5 V drop at 16 A wastes 80 W continuously, which is paid for every hour the circuit runs.